Thermocouple – measuring inserts (data sheet 8661)
model |
TTeMiAo / TTeMiAoT |
measuring element |
K, N, J and S according to DIN EN 60 584 |
operating temperature range |
type K, NiCr-Ni −40 / +1175 °C (−40 / +2147 °F) type N, NiCrSi-NiSi −40 / +1175 °C (−40 / +2147 °F) type J, Fe-CuNi −40 / +750 °C (−40 / +1382 °F) type S, Pt10Rh-Pt 0 / +1175 °C (+32 / +2147 °F) |
ambient temperature range |
TTeMiAo: −40 / +100 °C (−40 / +212 °F) TTeMiAoT: −40 / +85 °C (−40 / +185 °F) |
accuracy |
class 1 according to DIN EN 60 584 |
degree of protection |
IP 00 measuring inserts are intended for the installation into protective fittings for electrical thermometers, which are equipped with an appropriate degree of protection for safe operation |
output signal |
model TTeMiAo: thermoelectric voltage acc. to DIN EN 60 584 model TTeMiAoT: 4...20 mA, HART® or PROFIBUS® PA / FOUNDATION™ Fieldbus |
hot junction |
hot junction insulated |
Certificates
Data sheet download